Back to Toms River, New Jersey page
Table 3. Pump-characteristic data, calibrated values, and pump status during tests
Pump Location and Description |
EPANET Pump Curve ID |
EPANET Pump Id |
Initial Pump Curve (From Flegal, 1997) |
Calibrated Pump Curve |
Pump Status During Test |
|||
- | - | - | Flow (gal/min) | Head(ft) |
Flow(gal/min) |
Head(ft) |
March1998 |
August1998 |
Holly Plant Booster Pump 1 | C3-HOLLY1 | 20003 | 800.0 |
285.4 |
0.0 |
315.0 |
OFF |
ON |
900.0 |
270.4 |
810.0 |
243.0 |
|||||
1000.0 |
245.4 |
990.0 |
180.0 |
|||||
1100.0 |
200.3 |
- |
- |
|||||
Holly Plant Booster Pump 2 | C4-HOLLY2 | 20004 |
700.0 |
290.4 |
0.0 |
328.3 |
OFF |
ON |
800.0 |
280.4 |
784.0 |
274.0 |
|||||
900.0 |
265.4 |
1470.0 |
196.0 |
|||||
1000.0 |
255.4 |
- | - | |||||
1100.0 |
245.4 |
- | - | |||||
1200.0 |
235.3 |
- | - | |||||
1500.0 |
200.3 |
- | - | |||||
Holly Plant Booster Pump 3 | C5-HOLLY3 | 20005 |
1900.0 |
295.4 |
0.0 |
306.0 |
OFF |
ON |
2300.0 |
282.4 |
2430.0 |
238.5 |
|||||
2700.0 |
265.4 |
3150.0 |
189.0 |
|||||
3000.0 |
250.4 |
- | - | |||||
3300.0 |
233.4 |
- | - | |||||
3500.0 |
220.3 |
- | - | |||||
Parkway Booster Pump 1 | C22-PKWYB1 | 20022 |
1500.0 |
175.3 |
0.0 |
209.4 |
ON |
ON |
1800.0 |
167.2 |
1742.4 |
187.4 |
|||||
2000.0 |
158.2 |
3000.0 |
135.0 |
|||||
2200.0 |
146.2 |
3920.0 |
0.0 |
|||||
2400.0 |
132.2 |
- | - | |||||
2600.0 |
115.0 |
- | - | |||||
2800.0 |
103.0 |
- | - | |||||
Parkway Booster Pump 2 | C23-PKWYB2 | 20023 |
3100.0 |
209.3 |
0.0 |
240.0 |
OFF |
ON |
3600.0 |
202.3 |
3600.0 |
202.3 |
|||||
3900.0 |
193.3 |
4300.0 |
172.5 |
|||||
4300.0 |
173.2 |
- | - | |||||
Holiday City Booster Pump | C11-HCBP | 20011 |
500.0 |
134.0 |
0.0 |
220.0 |
ON |
ON |
700.0 |
130.0 |
900.0 |
200.0 |
|||||
900.0 |
126.2 |
1500.0 |
175.0 |
|||||
1200.0 |
119.0 |
- | - | |||||
1300.0 |
116.0 |
- | - | |||||
1500.0 |
107.0 |
- | - | |||||
Route37
(St. Catherines) Booster Pump |
C13-R37B | 20013 |
450.0 |
210.0 |
0.0 |
240.0 |
OFF |
OFF |
500.0 |
206.0 |
500.0 |
206.0 |
|||||
600.0 |
195.8 |
700.0 |
184.0 |
|||||
700.0 |
183.3 |
2200.0 |
0.0 |
|||||
South Toms River Booster Pump 1 | C24-STRB1 | 20024 |
0.0 |
320.4 |
0.0 |
320.4 |
OFF |
OFF |
100.0 |
315.5 |
300.0 |
290.0 |
|||||
200.0 |
305.4 |
600.0 |
210.0 |
|||||
300.0 |
290.4 |
975.0 |
0.0 |
|||||
400.0 |
275.4 |
- | - | |||||
500.0 |
250.4 |
- | - | |||||
600.0 |
210.2 |
- | - | |||||
South Toms River Booster Pump 2 |
C25-STRB2 |
20025 |
0.0 |
320.4 |
0.0 |
320.4 |
OFF |
OFF |
100.0 |
315.5 |
400.0 |
275.0 |
|||||
200.0 |
305.4 |
600.0 |
215.0 |
|||||
300.0 |
290.4 |
975.0 |
0.0 |
|||||
400.0 |
275.4 |
- | - | |||||
500.0 |
250.4 |
- | - | |||||
600.0 |
210.2 |
- | - | |||||
Windsor Booster Pump 1 | C19-WA1 | 20019 |
750.0 |
245.0 |
0.0 |
228.4 |
OFF |
ON |
850.0 |
242.3 |
739.5 |
210.5 |
|||||
950.0 |
236.3 |
957.0 |
194.9 |
|||||
1100.0 |
224.3 |
- | - | |||||
Windsor Booster Pump 2 | C20-WA2 | 20020 |
750.0 |
245.0 |
0.0 |
223.1 |
OFF |
ON |
850.0 |
242.3 |
705.5 |
200.9 |
|||||
950.0 |
236.3 |
880.0 |
179.2 |
|||||
1100.0 |
224.3 |
- | - | |||||
Windsor Booster Pump 3 | C21-WA3 | 20021 |
750.0 |
245.0 |
0.0 |
228.4 |
OFF |
ON |
850.0 |
242.3 |
739.5 |
210.5 |
|||||
950.0 |
236.3 |
957.0 |
194.9 |
|||||
1100.0 |
224.3 |
- | - |